EV charger cable size calculator

Work out the cable size for a home EV charger from its rated current, the length of the run and how the cable is installed. The calculator below starts with a 7.4 kW single-phase charger (32 A) on a 20 m run; change it to match yours.

Cable size (copper)–

Breaker rating In
–
Capacity after derating Iz
–
Voltage drop
–
Size set by
–

Copper conductors, IEC 60364-5-52 Annex B current-carrying capacities at 30 °C, temperature factors from Table B.52.14 (rounded up to the next 5 °C step) and grouping factors for bunched circuits from Table B.52.17. The breaker is the smallest standard rating at or above the load current, and the cable must carry at least that rating after derating (Ib ≤ In ≤ Iz). Not covered here: buried cables (method D), aluminium, fault-loop disconnection times and short-circuit checks. Guidance only: check the standard, the cable maker's data and your national wiring rules. The installer remains responsible for the design.

Typical sizes for home chargers

Copper PVC cable at 30 °C, not grouped with other circuits, sized for a 3% voltage drop on the charger circuit. The breaker equals the charger's rated current.

ChargerInstallation15 m30 m50 m
7.4 kW (32 A, 1-phase 230 V)C (clipped direct)4 mm²10 mm²16 mm²
7.4 kW (32 A, 1-phase 230 V)A1 (insulated wall)6 mm²10 mm²16 mm²
11 kW (16 A, 3-phase 400 V)C (clipped direct)1.5 mm²2.5 mm²4 mm²
11 kW (16 A, 3-phase 400 V)A1 (insulated wall)2.5 mm²2.5 mm²4 mm²
22 kW (32 A, 3-phase 400 V)C (clipped direct)4 mm²4 mm²6 mm²
22 kW (32 A, 3-phase 400 V)A1 (insulated wall)10 mm²10 mm²10 mm²

Why the rated current, not the power

A charger draws its full rated current for hours at a time, so IEC 60364-7-722 treats it as a continuous load: size the circuit for the charger's rated current, with no diversity. A 7.4 kW charger is a 32 A load. If the charger lets you set a lower current (for example 16 A), size the cable for the setting you will actually use, and remember it may be raised later.

Also check

Questions

What size cable do I need for a 7 kW EV charger?

A 7.4 kW charger draws 32 A on 230 V. Clipped direct over 15 m that is 4 mm², and at 30 m the voltage drop pushes it to 10 mm² (3% limit). Run through an insulated wall it needs 6 mm² even on a short run. Check your own length and installation in the calculator above.

What size cable for an 11 kW charger?

11 kW is 16 A per phase on 400 V three-phase. Clipped direct it needs 1.5 mm² at 15 m and 4 mm² at 50 m.

What size cable for a 22 kW charger?

22 kW is 32 A per phase on 400 V three-phase. Clipped direct it needs 4 mm² at 15 m and 6 mm² at 50 m; in an insulated wall 10 mm² at 15 m.

Can I rely on the result without checking?

No. It is guidance based on IEC 60364. Follow the charger's installation manual and your national wiring rules, which may add requirements. The installer remains responsible for the design.