Electrical & cables ·

What size breaker for a cable? Match the breaker to the cable (IEC 60364)

A circuit breaker rated 25 A between a load of 20 A and a cable rated 27 A, showing Ib ≤ In ≤ Iz

To choose a breaker for a cable, follow Ib ≤ In ≤ Iz: the breaker rating In must be at least the load current Ib and no higher than the cable's current-carrying capacity Iz. The breaker protects the cable, so a breaker bigger than the cable can carry lets the cable overheat before anything trips. This is the core overload rule in IEC 60364, and it is easy to apply once you have the corrected cable rating.

What Ib, In and Iz mean

If a load draws 18 A, any breaker from 20 A up can carry it, but only if Iz is at least that breaker rating too. The best choice is the smallest standard breaker above Ib that the cable also covers.

Typical breaker sizes for copper PVC cable

Using tabulated currents for two loaded conductors, PVC insulation, installation method C (clipped direct) before any derating:

CableTabulated IzCommon maximum breakerTypical use
1.5 mm²19.5 A10 ALighting circuits
2.5 mm²27 A20 ASocket circuits
4 mm²36 A32 ACookers, showers, EV chargers
6 mm²46 A40 ALarger showers, sub-mains
10 mm²63 A50 ASub-mains, heat pumps

The "common maximum" is lower than Iz on purpose: it leaves a margin for derating, and breakers come in fixed steps. Your national wiring rules may set different limits, so check them for the final design.

Worked example: an electric shower

An 8.5 kW shower on 230 V draws about 37 A, so Ib = 37 A.

  1. The next standard breaker above 37 A is 40 A, so In = 40 A.
  2. 6 mm² has Iz = 46 A in method C. That is at least 40 A, so it passes. 4 mm² (36 A) does not.
  3. If the cable is buried in warm insulation, apply a correction factor. At 0.8, Iz drops from 46 A to 36.8 A and the 6 mm² no longer covers a 40 A breaker. You would move up to 10 mm².

The check is simple, but the derating step is where many installs go wrong. The related guides on voltage drop on long cable runs show the next check you need.

Why a bigger breaker is dangerous

A breaker rated above Iz can let a sustained overload run through the cable. The cable heats beyond its insulation limit, 70 °C for PVC, with no trip. The fix is never "a bigger breaker": it is a bigger cable, or a lower-rated breaker, or a smaller load.

Checklist before you pick a breaker

Check it in seconds

Cable Calc runs all of these checks on one screen: cable size to IEC 60364, temperature and grouping derating, breaker rating and voltage drop. It works offline, so you can use it on site. If you prefer the browser, the free cable size calculator does the same sums. More guides are in our electrical and cables section.

Frequently asked questions

What size breaker do I need for 2.5 mm² cable?

For two-conductor PVC copper cable clipped direct (installation method C), 2.5 mm² carries about 27 A, so a 20 A breaker is the usual choice for socket circuits. After derating for heat and grouping the usable current can be lower, so check it.

Can I fit a bigger breaker than the cable rating?

No. The breaker must trip before the cable overheats, so its rating In must not exceed the cable's corrected current-carrying capacity Iz.

What does Ib, In and Iz mean?

Ib is the design current of the load, In is the rated current of the protective device, and Iz is the current-carrying capacity of the cable after correction factors. The rule is Ib ≤ In ≤ Iz.

Does voltage drop affect the breaker choice?

Not directly, but a long run can force a larger cable to keep voltage drop within limits. The breaker still must not exceed the cable's Iz, and short-circuit trip times matter on long runs.

Published: . More in Electrical & cables or all articles.